ModbusDeviceKit

🇬🇧 English | 🇹🇷 Türkçe

NuGet License: MIT

dotnet add package ModbusDeviceKit

A .NET 8 library that reads Modbus RTU/TCP devices (load cells, torque sensors, temperature/pressure transmitters…) described by JSON profile files. When a new device brand arrives, you add a JSON profile instead of hand-coding its register map.

  • Reads every register in one call and merges adjacent registers into a single Modbus request
  • Int16/UInt16/Int32/UInt32/Float32/Int64/UInt64/Float64/Bool with ABCD/CDAB/BADC/DCBA byte orders
  • Named, scaled results: value = raw × scale + offset − tare
  • Tare/calibration: ApplyTareAsync() (averaged samples), ApplyTare(), SetTare(), ClearTare()
  • Retries with Polly (constant/linear/exponential backoff, jitter) and automatic reconnect when the link drops
  • Meaningful exceptions: DeviceTimeoutException, DeviceConnectionException, DeviceSlaveException…
  • Modbus RTU (serial port), Modbus TCP and RTU-over-TCP (serial-to-Ethernet converters), built on NModbus
  • Fully async and thread-safe; several devices can share one RS-485 line (transport)
  • Field-ready: partial reads, automatic splitting of rejected blocks, opt-in writes, device probing and bus scanning

Quick start

using ModbusDeviceKit;

await using var reader = await DeviceReader.CreateFromFileAsync("device-profile.json");
await reader.ConnectAsync();

DeviceReading reading = await reader.ReadAsync();
double force = reading["Force"];                     // scaled value with tare applied
RegisterValue temp = reading.GetRegister("Temperature");
Console.WriteLine($"{temp.Value} {temp.Unit} (raw: {temp.RawValue})");

Dictionary<string, double> values = reading.ToDictionary();

await reader.ApplyTareAsync(samples: 10);            // zero every register with "allowTare": true

To create the transport yourself (e.g. several devices on the same RS-485 line):

using System.IO.Ports;
using ModbusDeviceKit.Profiles;
using ModbusDeviceKit.Transport;

await using var bus = new ModbusRtuTransport("COM3", 19200, Parity.Even);
using var loadCell = new DeviceReader(DeviceProfile.LoadFromFile("loadcell.json"), bus);
using var torque   = new DeviceReader(DeviceProfile.LoadFromFile("torque.json"), bus);

Profile format

{
  "deviceName": "LoadCell_XYZ123",       // required
  "protocol": "ModbusRTU",               // ModbusRTU | ModbusTCP | ModbusRtuOverTcp
  "slaveId": 1,
  "byteOrder": "ABCD",                   // default byte order: ABCD | CDAB | BADC | DCBA

  "connection": {                        // used by DeviceReader.Create / ModbusTransportFactory
    "serial": { "portName": "COM3", "baudRate": 9600, "parity": "None", "dataBits": 8, "stopBits": "One" },
    "tcp":    { "host": "192.168.1.50", "port": 502 },
    "connectTimeoutMs": 3000, "readTimeoutMs": 500, "writeTimeoutMs": 500
  },

  "retry": { "maxRetries": 3, "delayMs": 100, "maxDelayMs": 2000, "backoff": "Exponential", "useJitter": true },

  "readOptions": { "maxRegistersPerRead": 120, "maxAddressGap": 0, "interRequestDelayMs": 5,
                   "partialReads": true, "splitRejectedBlocks": true },

  "registers": [
    { "name": "Force", "address": 100, "dataType": "Float32", "scale": 0.01, "unit": "N", "allowTare": true },
    { "name": "Temperature", "address": 102, "dataType": "Int16", "scale": 0.1, "offset": -0.5, "unit": "C" },
    { "name": "AdcCounts", "address": 200, "registerType": "Input", "dataType": "Int32", "byteOrder": "CDAB" },
    { "name": "Overload", "address": 0, "registerType": "DiscreteInput", "dataType": "Bool" },
    { "name": "Setpoint", "address": 300, "dataType": "Int16", "scale": 0.1, "unit": "N", "writable": true }
  ]
}
Register field Default Description
name — Unique name (case-insensitive)
address — Zero-based protocol address (40101 → 100)
registerType Holding Holding (FC03), Input (FC04), Coil (FC01), DiscreteInput (FC02)
dataType UInt16 Bool is required for Coil/DiscreteInput
byteOrder profile value Per-register byte order
scale / offset 1 / 0 Calibration: raw × scale + offset
tare / allowTare 0 / false Initial tare; include the register in ApplyTare() (tare all)
writable false Allow WriteAsync (Holding and Coil only)
unit, description — Informational

Profiles are validated on load. Unknown fields (e.g. a "scael" typo) and inconsistent values are reported together in a single DeviceProfileException with the full error list. Comments are allowed in the JSON.

Error handling

Every connect/read operation is retried according to the retry settings. Timeouts, CRC/IO errors, dropped connections, "Slave Device Busy" (6), "Acknowledge" (5) and "Gateway Target Failed To Respond" (11) are treated as transient. Requests the device explicitly rejects, such as "Illegal Data Address", are not retried.

Exception When
DeviceTimeoutException The device did not answer in any attempt
DeviceConnectionException The port/socket could not be opened
DeviceSlaveException The device returned a Modbus exception response (ExceptionCode, ExceptionName)
DeviceCommunicationException CRC/framing/IO error (also the base class of the timeout and slave exceptions)
DeviceProfileException The profile is invalid (Errors list)

All of them derive from ModbusDeviceKitException. Communication errors carry DeviceName, SlaveId and Attempts; connection errors carry Endpoint and Attempts.

Field features

Partial reads. With "partialReads": true, a request that still fails after all retries no longer fails the whole reading: its registers come back with IsValid = false, a NaN value and an Error text, while the rest is read normally. An exception is thrown only when nothing at all could be read.

var reading = await reader.ReadAsync();
if (!reading.IsComplete)
    foreach (var failed in reading.FailedRegisters)
        Console.WriteLine($"{failed.Name}: {failed.Error}");

Rejected blocks. Many devices have holes in their register map and refuse a multi-register request that covers them. With "splitRejectedBlocks": true (default), when the device answers "Illegal Data Address" or "Illegal Data Value" to such a request, its registers are read one by one — and from then on without asking for the range again.

Writes. Registers marked "writable": true can be written with engineering values; the library converts back to raw units ((value − offset) / scale) and picks function 06, 16 or 05. Writes are opt-in, so a typo can never change a device setting.

await reader.WriteAsync("Setpoint", 125.5);   // N → raw 1255 → FC06

Probing and bus scan. ProbeAsync checks whether a device answers and explains what to check when it does not. A Modbus exception answer counts as "responded": the device is online, only the address is wrong. ModbusBusScanner does the same for a range of slave ids — handy when commissioning an RS-485 line.

DeviceProbeResult probe = await reader.ProbeAsync();
Console.WriteLine(probe.Message);

await using var bus = new ModbusRtuTransport("COM3", 19200, Parity.Even);
var found = await ModbusBusScanner.ScanAsync(bus, Enumerable.Range(1, 10).Select(i => (byte)i));
foreach (var result in found.Where(r => r.Responded))
    Console.WriteLine($"Slave {result.SlaveId} is online");

Console sample

dotnet run --project samples/ModbusDeviceKit.ConsoleSample                       # device-profile.json, every 5 s
dotnet run --project samples/ModbusDeviceKit.ConsoleSample -- my-device.json --interval 2
dotnet run --project samples/ModbusDeviceKit.ConsoleSample -- --simulate         # no hardware, built-in simulator

While running: T = tare (average of 5 samples), C = clear tare, Q/Esc = quit.

Build, test, pack

dotnet build
dotnet test
dotnet pack src/ModbusDeviceKit -c Release -o artifacts