| 1 | +# GOOSE Engineering Readout — P0–P3 Validation Handoff |
| 2 | + |
| 3 | +Date: 2026-10-21. Scope: receive-only GOOSE engineering workspace. Baseline: selection/inspector single-source-of-truth hotfix plus v1.4.2 GUI candidate. This is **not** an IEC 61850 conformance claim. |
| 4 | + |
| 5 | +## Engineering invariants |
| 6 | + |
| 7 | +1. Selection is keyed to source MAC, APPID, VLAN, and GoCB reference; transient WPF null/retransmission does not delete operator intent. |
| 8 | +2. **Live** Inspector always shows the latest coherent frame of the explicitly selected publisher. Choosing an event pins an immutable historical snapshot. Returning to Live explicitly clears timeline selection; switching publisher cannot leave a misleading historic highlight. |
| 9 | +3. RX frame count is distinct from event count **visible after filters**. Retransmission toggle governs only event history visibility; it does not stop receiving retransmitted packets. |
| 10 | +4. Raw MMS data without matching SCL is labeled `Entry 1…n` with its decoded wire type/value. Signal names, DPC meanings, and IEC 61850 q quality are never inferred from arbitrary bit patterns. |
| 11 | +5. Only a matched SCL quality field with a valid 13-bit MMS BIT STRING can be interpreted as IEC 61850 q. Invalid unused-bit padding, unexpected width, bad hex, and non-BitString types fail closed. |
| 12 | +6. The initial observed DataSet is a baseline, not a fabricated field change. Subsequent changes use prior observed values. |
| 13 | +7. Test-mode publishers show explicit **TEST** identifiers; no red/green Boolean good/bad assumptions. |
| 14 | +8. Keyed publisher rows and per-index DataSet rows survive passive refreshes without collapsing an opened MMS detail. Deliberately changing publisher or pinning a different event resets only that DataSet context. |
| 15 | + |
| 16 | +## Visual contract |
| 17 | + |
| 18 | +- Workspace shell and panel gutters: 8 DIP. GOOSE detail width: 460 DIP; other workspaces unchanged. |
| 19 | +- Compact Signal / Value rows with a subdued chevron, expanded MMS raw value and payload hex, semantically resolved quality details only with a matching SCL. |
| 20 | +- Publisher label and full reference available without high-contrast action ornamentation. |
| 21 | +- Timeline remains a forensic event list, not a decorative panel filled with unrelated cards. |
| 22 | +- Time-sensitive status strip reflects GOOSE traffic when the GOOSE workspace is active, without changing other workspaces' status. |
| 23 | + |
| 24 | +## Required automatic gates |
| 25 | + |
| 26 | +Windows repository health, workspace layout/source contract, full .NET solution compilation, unit tests, Runtime Stability, Runtime Architecture, CodeQL, dependency checks and Inno installer package/install/repair. These must all reference the *same commit SHA* and be verified on the PR head. |
| 27 | + |
| 28 | +### Regression coverage |
| 29 | + |
| 30 | +- Empty/malformed quality, invalid unused padding, exact 13-bit validity values, substituted/test/operator-blocked detail flags. |
| 31 | +- Generic entry names versus explicit matching SCL signal reference names. |
| 32 | +- Publisher TEST flag changes on an existing selected keyed row. |
| 33 | +- Multi-publisher identity, retransmission, same-GoID split MAC/VLAN, filter-miss, stale/recovery, 1,000 retransmissions, 500-source bounded churn. |
| 34 | +- First-frame baseline versus later observed state-change semantics. |
| 35 | + |
| 36 | +## Manual Windows field acceptance (still required after automated PASS) |
| 37 | + |
| 38 | +At 1366×768, 1586×893 and 1920×1080 (where available) under 100%, 125%, and 150% display scaling: inspect normal/expanded DataSet rows without clipping, confirm chevron click and keyboard toggle, tab through TEST/LIVE/PINNED/STALE indicators, select multiple GOOSE publishers during continuous retransmissions, pin events, click Return to Live, use filter search/GOOSE ID with no selection loss, and observe updates with real or recorded GOOSE traffic. Import a matching SCL and verify genuine signal/quality mappings, then repeat without SCL to confirm raw-only fallback. |
| 39 | + |
| 40 | +**Acceptance boundary:** a successful automated CI build does not prove physical UI readability or IEC 61850 interoperability at a specific field installation. Keep candidate publication and branch promotion separate from this manual sign-off. |
| 41 | + |
| 42 | +## Follow-up: operator screenshot inspection, expanded raw MMS entries |
| 43 | + |
| 44 | +Three operator screenshots of the P0–P3 candidate demonstrate selection stability during reception and successful simultaneous expansion of two typed DataSet entries. They also reveal three visual defects: DataSet title/count running together, the Inspector context disappearing when the entire pane scrolls, and unnecessarily tall expanded MMS details. |
| 45 | + |
| 46 | +The targeted follow-up uses a fixed Inspector header row (including PINNED/TEST and Return to Live), a single scrolling evidence region, an explicitly aligned DataSet title/count grid, and compact key/value MMS details. These corrections do not alter packet reception, GOOSE state matching, generic typed decoding, or the 8-DIP workspace gutter. |
| 47 | + |
| 48 | +Required physical acceptance: expand two entries, scroll to the bottom and back, confirm the Inspector mode and Return to Live remain visible throughout; confirm the DataSet count does not touch the title at 100%, 125%, 150% DPI; verify selecting a different publisher or returning to Live changes Inspector context correctly without replacing unrelated publisher rows. |
| 49 | + |
| 50 | +## Operator language acceptance — message/field terminology |
| 51 | + |
| 52 | +The application must explain what an electrical engineer is seeing without requiring familiarity with every IEC 61850 field name. Keep accurate original wire references in tooltips or expandable forensic rows. |
| 53 | + |
| 54 | +| Main display | Original technical evidence | |
| 55 | +| --- | --- | |
| 56 | +| Message name | goID | |
| 57 | +| Control block | goCbRef | |
| 58 | +| Application code | APPID | |
| 59 | +| State number / Sequence number | stNum / sqNum | |
| 60 | +| Sender address / Group address | Ethernet source / destination MAC | |
| 61 | +| Network group | VLAN ID and priority | |
| 62 | +| Configuration version | confRev | |
| 63 | +| Allowed wait | timeAllowedToLive, milliseconds | |
| 64 | +| Binary bit pattern | MMS BitString | |
| 65 | +| Data item 1, Data item 2… | Raw decoded values without matching SCL | |
| 66 | +| Open/Closed (verified switch-position signal only) | Matched SCL XCBR or XSWI / Pos.stVal | |
| 67 | +| First seen / State changed / Repeated | New / State Change / Retrans reception events | |
| 68 | + |
| 69 | +**Failure safety:** no breaker position can be inferred from a bare `00/01/10/11` bit pattern, unrelated DPC attributes, quality fields, timestamps or incomplete SCL identity. Source data is not renamed when evidence is missing. A configuration-tab shortcut explains how to identify signals. |
| 70 | + |
| 71 | +**Clock semantics:** the reception time in message history must use the same local clock as the recorded-message Inspector timestamp, avoiding false multi-hour offsets on site. |
| 72 | + |
| 73 | +**Additional physical acceptance:** use a multi-publisher real capture and a matching imported device configuration. Compare message history time against the Inspector time; validate names, interpreted switch position and decoded quality against a separately verified record. With no configuration, all entries remain generic with readable data type and raw bit/hex evidence. Test 100/125/150% scaling and expand two data rows without losing the sticky Inspector heading. |